cables for marine power cable detailed description:
1 Rated voltage(Uo/U): 150/250V or 600/1000V.
2 The Max. permissible continuous operating temperature of conductor:90℃.
3 The Min. laying temperature:0℃. It should be pre-heated if it is below the Min. laying temperature.
4 The permitted bending radius: No less than 12 times of the overall diameter of the cable.
5 Flame characteristic
5.1 The cable can pass the test according to IEC 60332-3-22: Test method on electrical wires or cables under fire condition, Test for vertical flame spread of vertically-mounted bunched wires or cables-Category A.
5.2 The cable can pass the test according to IEC 60332-1: Test on electric and optical fiber cables under fire conditions, Test for vertical flame propagation for a single insulated wire or cable-Apparatus.
5.3 The cable can pass the test according to IEC 61034: Test method on electrical wires or cables under fire condition, Measurement on smoke density of wire or cables. The insulation and sheath material of the low-smoke halogen-free flame retardant cable should be tested as per IEC 60754-1 and IEC 60754-2, which HCl content is less than 5mg/g,
PH is no less than 4.3 and conductivity should be less than 10μs/mm.
6 Fire resistance characteristics It can pass the fire resistance test
according to IEC 60331-21 Standards.